11kv 15A Expulsion Fuse Link

Breaking Capacity: High
Type: Distribution
Usage: High Voltage
Shape: Circle
Fusing Speed: T K
Fusing Device: Fuse Link
Customization:
Diamond Member Since 2015

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
11kV 15A
Standard
IEC IEEE
Size
500
Long
660mm
a
100-200A
Transport Package
Cartons Pallets Wooden Case
Specification
IEC IEEE
Trademark
OEIpower
Origin
China Nanyang
HS Code
8535309000
Production Capacity
100000

Product Description

 The Fuse Cutout type OEI was developed to operate in overhead distribution systems rated at 11
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link11kv 15A Expulsion Fuse Link
S/N Description Units Schedule A Schedule B
1 Current ratings A 5  
2 Frequency Hz 50  
3 Rated Speed ratio   Type K as per IEC
60282 -2
 
4 Class of fuse link   Class B as per IEC
60282-2
 
5 Fuse element   Tin or Silver  
6 Following Routine test results shall be provided on delivery of fuse links  
 
 
 
Yes/No
a) a static strength test; and Yes  
b) a resistance test, with the
fuse-link under strain.
 
 
 
Yes
 
7 The following tests shall be performed on one fuse-link per batch and
test results provided on
delivery of  fuse links:
 
 
 
 
Yes/No
 
a)confirmation of the time/current characteristics; and
 
 
 
 
Yes
 
b) a dynamic strength test. Yes  
8 Drawing showing construction and dimensions as per figure
1 below to be provided
with bid
Yes/No Yes  
9 Previous type tests reports/certificate to be
provided on bid.
 
Yes/No
 
Yes
 
10 Altitude above sea level m 1400  
11 Ambient operating oC -1 to 40  
Performance Characteristic
Applied standard IEEE C37.42-2009
Catalog number  
Nominal system voltage kV 22
Rated Frequency Hz 50
Rated m aximum(design) voltage 27
Rated Continuous current A-RMS 100
Rated Interrupting current asymmetrical/symmetrical A-RMS 12000/8000
BIL 1.2x50 µs kV-peak 125
Minimum critical impulse flashover voltage(CFO)KV peak 140
Dry withstand voltage kV-RMS 42
Wet withstand voltage kV-RMS 36
Creepage distance to group Min.mm 320
Minimum creepage factor of insulator (Creepage Distance/arcing distance) 2
Performance Characteristic
Applied standard IEC60282-2
Catalog number  
Nominal system voltage kV 11
Rated Frequency Hz 50
Rated m aximum(design) voltage 12
Rated Continuous current A-RMS 100
Rated Interrupting current asymmetrical/symmetrical A-RMS 12000/8000
BIL 1.2x50 µs kV-peak 125
Minimum critical impulse flashover voltage(CFO)KV peak 140
Dry withstand voltage kV-RMS 42
Wet withstand voltage kV-RMS 36
Creepage distance to group Min.mm 372
Minimum creepage factor of insulator (Creepage Distance/arcing distance) N/A
Performance Characteristic
Applied standard IEEE C37.42-2009
Catalog number  
Nominal system voltage kV 33
Rated Frequency Hz 50
Rated m aximum(design) voltage 38
Rated Continuous current A-RMS 100
Rated Interrupting current asymmetrical/symmetrical A-RMS 8000/5000
BIL 1.2x50 µs kV-peak 150
Minimum critical impulse flashover voltage(CFO)KV peak 165
Dry withstand voltage kV-RMS 70
Wet withstand voltage kV-RMS 60
Creepage distance to group Min.mm 650
Minimum creepage factor of insulator (Creepage Distance/arcing distance) 2.3
 
  DIMENSION(mm)
RATED CURRENT
(A)
A B C D L MN
1 to 25 12.5+0.2 19.0+0.2 6.5 2.0 533,600,787
30 to 40 12.5+0.2 19.0+0.2 8.0 3.0 533,600,787
50 to 100 19.0+0.3 not applicable 9.0 5.0 533,600,787
140 to 200 19.0+0.3 not applicable 13.0 7.0 533,600,787

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2015

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory & Trading Company
Management System Certification
OHSAS18001:2007, ISO 9001: 2015 Certificate, ISO 14001:2015 Certificate