Compact Oil Immersed Power Distribution Transformer

Product Details
Customization: Available
Application: Power
Phase: Three
Still deciding? Get samples of $ !
Order Sample
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.
Manufacturer/Factory & Trading Company

360° Virtual Tour

Secured Trading Service
Diamond Member Since 2015

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
OHSAS18001:2007, ISO 9001: 2015 Certificate, ISO 14001:2015 Certificate
  • Compact Oil Immersed Power Distribution Transformer
  • Compact Oil Immersed Power Distribution Transformer
  • Compact Oil Immersed Power Distribution Transformer
  • Compact Oil Immersed Power Distribution Transformer
  • Compact Oil Immersed Power Distribution Transformer
  • Compact Oil Immersed Power Distribution Transformer
Find Similar Products

Basic Info.

Model NO.
S11
Core
Core-type Transformer
Cooling Method
Oil-immersed Type Transformer
Winding Type
Two-winding Transformer
Usage
Power Transformer, Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Oeipower
Product Name
Oil Immersed Transformer
Type
Oil-Filled Transformer
Material
Copper / Aluminium
Vector Group
Dyn11 / Yyn0
Transformer Type
S11 Oil-Immersed Transformer
Warranty
2 Years
Coil Material
Aluminum/Copper
Frequency
50/60Hz
Connection Group
Yyn0/Dyn11
Transport Package
Wooden Case
Trademark
OEI power
Origin
China
HS Code
8504220000

Packaging & Delivery

Package Size
1500.00cm * 1500.00cm * 2000.00cm
Package Gross Weight
1000.000kg

Product Description

Compact Oil Immersed Power Distribution Transformer
Main Components:
The primary components of this transformer include the Oil Tank, Conservator, Buchholz Relay, Breather Unit, Oil Indicator, Temperature Detector, Pressure Relief Device, Thermal Relay, Radiator, and Bushing.
1. The oil tank is designed to immerse the windings, ensuring optimal cooling and insulation.
2. Complies with IEC standards and holds CE/ISO certificates.
3. Allows easy contact and expansion during load changes, thereby increasing and decreasing the oil temperature efficiently.
4. The Buchholz relay is utilized when a conservator tank is present, indicating issues such as low oil levels and improper oil flow between the tank and transformer.
5. The Breather Unit contains silica gel, which absorbs moisture in the oil, changing color from blue to pink once it is saturated and can no longer absorb moisture.
6. The oil indicator shows the oil level within the conservator unit, providing essential monitoring.
7. The temperature detector monitors the oil's temperature, disconnecting the transformer from service if the temperature rises too high.
8. The pressure relief device reduces internal pressure to prevent transformer explosion, ensuring safety.
9. The thermal relay acts as an indicator for the winding temperature, providing crucial data for maintenance.
10. Fully galvanized coating ensures no rust, enhancing durability.
11. The bushing connects the internal windings to the external electrical network, facilitating smooth power distribution.
 
Rated capacity (KVA) Connection symbol Volatge combination No-load loss(W) Load loss(W) No-load current(%) Short circuit impedance(%) Dimension(mm) weight(kg)
High-voltage Tapping rang Low-voltage L×W×H
30 Dyn11 or Yyn0 11
  10.5
 10
 6.3
 6
±2×2.5% 0.693
  0.4
130 630 2.1 4 800×500×890 320
50 17 910 2 800×650×910 430
63 200 1090 1.9 850×650×920 450
80 250 1310 1.8 850×750×930 500
100 290 1580 1.6 1010×760×960 630
125 340 1890 1.5 1020×720×970 660
160 400 2310 1.4 1030×720×1000 745
200 480 2730 1.3 1040×720×1080 865
250 560 3200 1.2 1080×750×1100 1030
315 670 3830 1.1 1320×940×1160 1160
400 800 4520 1 1370×920×1180 1395
500 960 5410 1 1410×1000×1280 1675
630 1200 6200 0.9 4.5 1410×1000×1340 2020
800 1400 7500 0.8 1580×1070×1360 2380
1000 1700 10300 0.7 1730×1220×1420 2660
1250 1950 12000 0.6 1980×1280×1490 3280
1600 2400 14500 0.6 1920×1360×1590 4040
2000 2850 19500 0.6 5 1980×1470×1660 4900
2500 3000 21200 0.6 2200×1500×2300 5800
Ideal Service Environment
1. Device Types: Robust and Reliable Outdoor Models
2. Voltage Regulation Types: Versatile Off-circuit or On-load Options
3. Tapping Range: Flexible ±5%, ±2x2.5%, and ±4x2.5% Configurations
4. Frequency Compatibility: Choose Between 50Hz or 60Hz
5. Phases: Available in Three or Single Phases
6. Connection Symbol: Dyn11, Yyn0 (or Custom Configurations Upon Request)
7. Short-Circuit Impedance: Adheres to Standard Specifications
8. Optimal Operating Conditions: Altitude ≤ 1000m, Ambient Temperature ≤ 40°C. If these conditions aren't met, we can adjust parameters to meet the standard requirements.
Compact Oil Immersed Power Distribution TransformerCompact Oil Immersed Power Distribution TransformerCompact Oil Immersed Power Distribution TransformerCompact Oil Immersed Power Distribution TransformerCompact Oil Immersed Power Distribution TransformerCompact Oil Immersed Power Distribution TransformerCompact Oil Immersed Power Distribution Transformer