3.6 | The throat of the staple will present a diameter range |
mm | 26.42 | |||||||
3.7 | Throat Suspension Clamp support must have curvature, to allow an angle of entry and exit from the driver, |
º | 30º | |||||||
3.8 | Suspension clips present a breaking load |
kg | 11,340 | |||||||
3.9 | Minimum weight of zinc deposited in the hot galvanized steel |
g/m² | 915 | |||||||
3.10 | Minimum weight of zinc deposited in bolts, nuts and washers |
g/m² | 400 | |||||||
3.11 | Dimensions and drawings | mm | yes | |||||||
3.12 | ASTM standards | ASTM 123/153 |
Material
Connector bodies made of corrosion resistant, high strength aluminum alloy 99.5
Bolts: DIN 933, steel 8.8, dacromet; Nut: DIN934, dacromet, pressed into lower part
Pressure pad: aluminum alloy; Spring washer: DIN127, steel
Conical washer/Spring washers: Steel, DIN6796 corrosion-protected, dacromet
4.3 | The body material will be alloy of aluminum, bolts, washers and nuts of the fastening system of the staple will be hot dip galvanized forged steel |
yes | ||||||||
4.3 | ACSR 556 conductor diameter. 4MCM not including the rod |
mm | 23.54 | |||||||
4.5 | Breaking load | kg | ||||||||
4.6 | The compression type anchor clips for the conductor must be supplied with a connection terminal that can be bolted |
0° o 30°. | ||||||||
4.7 | Weight of zinc deposited on steel | g/m² | 915 g/m². | |||||||
4.8 | Zinc weight deposited on bolts, nuts and washers | g/m² | 400 g/m². | |||||||
4.9 | Weight | kg | ||||||||
4.1 | Dimensions and drawings | yes | ||||||||
4.11 | ASTM standards | ASTM 123/153 | ||||||||
4.12 | Attach to the staple | Norma IEC 60471. |
Stainless steel A2 bolts and nuts available according to order.
6.3 | The construction material of the splice must be aluminum and aluminum alloy must contain a maximum of 0.1% copper |
yes | ||||||||
6.4 | ACSR conductor section 556.4MCM |
mm² | 327.93 | |||||||
6.5 | Length | m | ||||||||
6.6 | Breaking load | kg | ||||||||
6.7 | Repair splices for the conductor must be preformed rods of the Armor Splice Full type Tension." |
yes | ||||||||
6.8 | Each rod that forms the joint must have a mark in its center with indelible ink |
yes | ||||||||
6.9 | Weight per unit | kg |