Basic Info.

Model NO.
55 - 4
Structure
Suspension Insulator
Type
A Type Insulator
Usage
High Voltage Power Transmission
Connection Method
Trough Type
Size of Bearing Capacity
160KN
Certification
ISO9001, IEC IEEE
Color
Grey
Brand
Oei Power
Transport Package
Cartons Pallets Wooden Case
Specification
IEC IEEE
Trademark
OEIpower
Origin
China Nanyang
HS Code
854690000
Production Capacity
100000

Product Description

Pin type insulator, ANSI CLASS 55 - 4

Pin Type Insulator, ANSI Class 55 - 4NECK size "F" typical application 13.2 KV. Flashover voltage: Impulse critical 1.2x50 Mu sec wave
Positive: 105 KV.
Negative: 130 KV. 60 Hz: Dry 65KV. Wet 35 KV.
Radio influence voltage: Test voltage to ground 10 KV. - Max RIV at 1000 Hz:100 Microvolts. Leakage distance: 9 inches
Dry arcing distance: 5 inches Cantilever strength: 3000 pounds
Pinhole Diameter-Threaded porselein: 1 inch Recommended pin length: 6 inches.
Type of glaze: Silen type


Pin Type Insulator, ANSI Class 55 - 4Pin Type Insulator, ANSI Class 55 - 4Pin Type Insulator, ANSI Class 55 - 4Pin Type Insulator, ANSI Class 55 - 4Pin Type Insulator, ANSI Class 55 - 4Pin Type Insulator, ANSI Class 55 - 4Pin Type Insulator, ANSI Class 55 - 4Pin Type Insulator, ANSI Class 55 - 4
The Composite Insulators comply with the latest editions of and amendments to, the standards/specification listed below:

 
CSA                                   CANADIAN STANDARDS ASSOCIATION
 
G164-4                        -       Hot dip galvanizing of Irregular Shaped Articles
 
CAN/CSA                  -       Quality Assurance Program Categories 2299.3
 
ANSI                           -      AMERICAN NATIONAL STANDARDS INSTITUTE
 
C29.1                           -      American Standard Test Method For Electrical Power Insulators
 
C29.7                           -      American Standard For Wet-processed Porcelain Insulators (High Voltage Line Post Type) Electrical Power Insulators
 
987-1985                     -       IEEE Guide For Application of Composite Insulators
 
D750                            -      Recommended Practice for Operating Light and Weather Exposure Apparatus (Carbon Arc Type) For Artificial Weather Testing Of Rubber Compounds.
 
D1499                          -      Recommended Practice For Exposure of Plastics.
 
D2240                          -      Rubber Properties, Durometer Hardness
 
D2565                          -      Recommended Practice For Operating Xenon-Arc Light And Water Exposure Apparatus Plastics.
The weathershed of the Post Insulators shall be manufactured from either Hydrated Alumina Ethylene Propylene Copolymer (EPM) as the primary constituent or Silicone Elastomers. The weathershead shall be injection moulded and brought to final cure state in one continuous process to prevent internal undercure or surface overcure. Additionally, the weathershead shall provide hydrophobic surface, even after exposure to tropical marine environment, ultra violent rays and moisture.
Core

 
The rod or the core is manufactured from Fibreglass, having 70-75 by weight of auxiliary aligned glass fibre bonded by an organic resin. The rod is either be cast or pultruded.
The end fittings are have the following properties:
 Pin Type Insulator, ANSI Class 55 - 4
i.          are compressed onto the Fibreglass rod member
ii.         are  not move relative to the central Fibreglass rod at applied loads equal to two times the rated Routine Test Load or maximum designed cantilever loads
iii.        are attracted to the rod after completion of all external heat processes used to cure or bond component parts.
 
The insulator are  provided load limiting bases that will deform under longitudinal loading of more than 100% of the rated design cantilever load. 
Performance Characteristics
 
The Polymeric Insulators are meet the under listed performance characteristics.
 
 
             ITEM
 
                11kV
 
                33KV
 
Dry Flashover Withstand
 
                90kV      
 
                180kV
 
Wet flashover withstand
 
                70kV
 
                165kV
 
Positive Impulse Critical flashover
 
               145kV
 
                300kV
 
Maximum Radio Interference Voltage
 
Below 1micro volt
 
   Below 1 micro volt         
 
Design Tension Strength
 
                100kN
 
                 100kN
 
Residual Strength after Power Arc
 
                  80kN
 
                   80kN
 
Mechanical Proof Test Load
 
                 45kN
 
                   45kN
 
Maximum Sustained Load
 
                 34kN
 
                   34kN
 
Design Torque Rating
 
                83 Nm
 
                   83 Nm
 
 Pin Type Insulator, ANSI Class 55 - 4
The insulator are suitable for accepting both aluminium and copper conductors having cross-sectional areas ranging from 35mm2 to 265mm2. The insulators are designed for mounting on the angle and channel crossarms specified in Specification E14
 
All exposed ferrous part shall be treated against corrosion. Treatment by hot dip galvanizing is preferable.
 
 
 