N/O | DETAIL | DATA | ||
1 | Description | Solid link assembly complete with link rated at 200A and mounting bracket to PIESA 002. (See Figure 1 to Figure 12 below) |
||
2 | System conditions of service a) nominal Voltage (Un) r.m.s |
kV |
11 |
|
b) maximum system voltage (Um) r.m.s | KV | 12 | ||
c) earthing | Effective & non effective | |||
d) Frequency | Hz | 50 | ||
3 | Site conditions of service a) altitude |
m |
1400 |
|
b) Operating Ambient temperature | °C | -1 to 40 | ||
c) Humidity | % | 85 | ||
4 | Rating | |||
a) Nominal voltage | kV | 11 | ||
b) Rated current | Solid link | A |
200 |
|
Cut out base |
A |
200 |
||
5 | Electrical components | |||
a) Insulator material specification | Porcelain | |||
Dielectric strength | ||||
Lightning impulse withstand (1.2/50) | kV | 95 | ||
Power frequency wet withstand voltage r.m.s |
kV | 28 | ||
6 | Specific creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: Drawings and brochures showing outline and general arrangement |
Yes/No |
Yes |
b) Detailed drawings of all items showing critical tolerances to be provided with bid |
Yes/No | Yes | |
8 | Previous Type test report/certificate on complete solid link assembly to be provided with bid |
Yes/No |
Yes |
10 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
11 | Applicable standard | PIESA 002 | |
12 | Other applicable standards | NRS 035 SABS IEC 60282-2 SABS IEC 60186 BS 137 part 2 |
N/O | DETAIL | DATA | |
1 | TYPE | 11kV pre-assembled gang operated overhead line load break switch complete with expulsion interrupters |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 11 | |
b) maximum voltage (Um) r.m.s | KV | 12 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 400 | |
f) Fault closing capacity | kA | 12.5 | |
4 | Site conditions of service a) altitude |
metres |
1400 |
b) Operating Ambient temperature | °C |
-1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 95 |
Power frequency wet withstand voltage r.m.s | KV | 28 | |
Short time current rating -1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: Drawings and brochures showing Outline and general arrangement |
Yes/No |
Yes |
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes. |
9 | Routine tests (acceptance tests on sample Product) to be provided on delivery. |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
N/O | DETAIL | DATA | |
1 | TYPE | 33kV pre-assembled gang operated overhead line load break switch complete with expulsion interrupters |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 33 | |
b) maximum voltage (Um) r.m.s | KV | 36 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 200 | |
f) Fault closing capacity | kA | 12.5 | |
4 | Site conditions of service a) altitude |
metres |
1400 |
b) Operating Ambient temperature | °C |
-1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 170 | |
Power frequency wet withstand voltage r.m.s | KV | 70 | |
Short time current rating -1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Drawings and brochures showing Outline and general arrangement |
Yes/No |
Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
N/O | DETAIL | DATA | |
1 | TYPE | 11kV pre-assembled gang operated overhead line switch without expulsion interrupters (non-load break switch) |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 11 | |
b) maximum voltage (Um) r.m.s | KV | 12 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 400 | |
4 | Site conditions of service a) altitude |
metres |
1400 |
b) Operating Ambient temperature | °C |
-1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 95 | |
Power frequency wet withstand voltage r.m.s | KV | 28 | |
Short time current rating -1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Drawing and brochures showing Outline and general arrangement |
Yes/No |
Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
N/O | DETAIL | DATA | |
1 | TYPE | 33kV pre-assembled gang operated overhead line switch without expulsion interrupters (non-load break switch) |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 33 | |
b) maximum voltage (Um) r.m.s | KV | 36 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 200 | |
4 | Site conditions of service a) altitude |
metres |
1400 |
b) Operating Ambient temperature | °C |
-1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 170 | |
Power frequency wet withstand voltage r.m.s | KV | 70 | |
Short time current rating -1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Drawing and brochures showing Outline and general arrangement |
Yes/No |
Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |