Seccionador Disconnector

Product Details
Customization: Available
Type: High-voltage
Structure: Three-column Disconnector
Still deciding? Get samples of US$ 1/Piece
Request Sample
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2015

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
OHSAS18001:2007, ISO 9001: 2015 Certificate, ISO 14001:2015 Certificate
  • Seccionador Disconnector
  • Seccionador Disconnector
  • Seccionador Disconnector
  • Seccionador Disconnector
  • Seccionador Disconnector
  • Seccionador Disconnector
Find Similar Products

Basic Info.

Model NO.
PRW-15/27
Installation
Outdoor High-voltage
Operation
Manual
Grounding Mode
Grounding
Movement Mode
Horizontal Rotary Type
Number of Poles
Three Pole
Grounding
Single Ground
Series
Three
Run
Turn the Horizontal
Common Model
Ist
Structure of Operating
Manual
Certification
IEC IEEE
Brand
Oei Power
Transport Package
Wooden Case
Specification
IEC IEEE
Trademark
OEI Power
Origin
China Nanyang
HS Code
8535309000
Production Capacity
7000

Product Description

Seccionador DisconnectorSeccionador DisconnectorSeccionador DisconnectorSeccionador DisconnectorSeccionador DisconnectorSeccionador DisconnectorSeccionador DisconnectorTECHNICAL SPECIFICATIONS
 Seccionador Disconnector
Single Pole Switch Isolator, 22kV, 800/630A
 
1.0  General
 
The single pole switch isolator are used for isolating feeders and lines.
 
2.0  Service Conditions
 
a.    Ambient Temperature    :       5°C - 50°C
b.    Relative Humidity           :       95% at 45°C (Tropicalised)
c.    Environmental condition: Tropical climate with polluted atmosphere
 
3.0  System Parameters
 
 The switch shall be used on a network having the following characteristics:-
a.    Nominal voltage            : 22 kV
b.    Maximum voltage         :    24 kV
c.    Earthing Arrangement  :    Effectively earthed
d.    Frequency                       :    50 Hz
 
4.0  Standards
Seccionador Disconnector
 
The item  conform to IEC 60129 or IEC62271-102 Ed.1.0 (2001)-Alternating current disconnectors & earthing switches or any other equivalent international standards.
It will be the responsibility of our to prove equivalency of his standard with one of these 2 standards mentioned above.
 
 
5.0  Technical requirements
 
a.    Rated voltage                          : 24kV
b.    Rated continuous current     :  630A
c.    Impulse Voltage Level (BIL)  : 150kV
d.    Rated Short time withstand current : 25kA/1 sec
e.    Rated peak withstand current  : 62kA
f.     Creepage Distance                      : 600mm
Seccionador Disconnector
 
6.0  Basic Features
 
      The isolating switch  have the following characteristics;
         -  Single pole type suitable for outdoor use
         -  Double insulator construction
         -  Fitted with appropriate latching device to prevent accidental opening due to faults, line vibration, wind or other environmental influences
        - Operated by portable insulated hook stick
       -      Suitable for underslung or vertical mounting
       -   Fitted with Tin plated palms suitable for Copper and Aluminium compression     lugs
      -  The palms are suitable to accommodate conductor AAAC 150mm2 to BSEN50183: 2000 or armoured cable XLPE insulated 300mm2 Copper or 240mm2 Aluminium to IEC 502
- Incoming and outgoing conductor/cable are connected on fixed parts and not on rocking parts
 
Information to be furnished with the offer
 
The following are furnished with the offer:
a)    Type Test Reports conforming to the relevant IEC Standards
b)    Catalogues, Technical literature and dimensional drawings of the item offered
c)    Detailed list of components
d)   Duly filled Schedule of guaranteed particulars (Annexure A).
e)    ISO 9001:2000 Certificate including the requirements as defined by clause 7 of the ISO 9001:2000 Standard.
f)     A list of the supplier's orders for the last five years.
 

 

GUARANTEED PARTICULARS

 
Single pole switch isolator, 22kV , 800/630A
 
POV2568
 
 
Serial No. Description    
1. Manufacturer's Reference name/code    OEIpower
2. Drawing No.    IS-24
3. Country of Origin    
4. Standard specifications to which the switch conform   IEC62271-102
5. Rated Voltage kV 24
6. Rated frequency Hz 50
7. Rated continuous current A 630
8. Rated short time current 
duration                                   
kA
 
sec
25kA/1 sec
9. Impulse voltage withstand
1.2/50µ S                                                              
 
kV
150
10. Total creepage distance                      mm 600
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now